Autoflo Model 200P

Minimize



   

Features

  • Uses patented "Convair Cone" for increased airflow through media
  • Uses minimal water and electricity
  • Durable stainless steel and thermoplastic cabinet resists rust, corrosion, and warping
  • Interior components designed for easy cleaning and replacement
  • Output capacity of 14.0 gallons per day (GPD)

Specifications

  • Size: 11-1/2" high x 12-1/8" wide x 7" deep
  • Plenum Opening: 6-1/8 in. high x 8-1/4 in. wide
  • Bypass Opening: 6 in. Diameter
  • Drum Motor: 24 VAC, 3.5 watts, 1 RPM
  • Evaporative Pad: 8" Diameter

Moisture Output Capacity

  • LBS. Per Hour: 4.86
  • Gallons Per Hour (GPH): 0.58
  • Gallons Per Day (GPD): 14.0

SEQUENCE OF OPERATION

The AUTOFLO Model 200P Humidifier uses the evaporative by-pass principal to add moisture into the return air duct of your central heating system.  A by-pass humidifier depends upon the air pressure difference between the warm air (supply) duct and the cold air (return) of the furnace.  This pressure differential causes a portion of the warm air to flow from the supply to the return through the humidifier.  A water pan at the bottom of the humidifier serves as a reservoir.  The water level in the reservoir is automatically controlled by a float valve assembly.  The motor driven media wheel is partially submerged in the water pan and partially exposed to the warm air flowing through the humidifier.  Upon a demand for humidity from the humidity control, water is evaporated as the by-pass system forces warm air through the wet rotating media wheel.  When this moisture laden air enters the return duct it is mixed with cool dry air flowing through the duct.  This air mixture will gradually increase the relative humidity in the home or office.

mounting location

RECOMMENDED LOCATION

TEMPERATURE AND SEFETY REQUIREMENTS

Refer to the rating plate on the furnace for minimum clearance to combustible construction.  All parts and connections of an AUTOFLO humidifier must be installed outside of the minimum clearance requirements for rear, top, sides, and flue of furnace.  Do not install where humidifier or water connections may be exposed to freezing temperatures or outside weather.  Attic installations are NOT recommended.  If you have central air conditioning, carefully plan the location of the plenum opening to prevent damage to the cooling coil or other devices inside the duct.

HUMIDIFIER MOUNTING LOCATION

All of the above models can be mounted on the supply or the return duct of the furnace.  Plan your location carefully with ease of installation and service in mind.
















STEP BY STEP INSTALLATION

CAUTION: Installation should be performed by qualified personnel only.  Use eye protection  and gloves when drilling and handling sheet metal.  All work must be performed to local and national codes and ordinances.  Use multi-conductor 18 awg. solid copper wire.  Provide over-current protection as required.  DO NOT omit the drain or overflow tubing.


ATTACH TEMPLATES AND CUT OPENINGS

Tape the mounting template to the chosen location.  Use a level or plumb line to make sure the template is level.  Before proceeding, verify that adequate clearances are available for servicing the media wheel and removing the water pan.  If necessary relocate the template.  Extend and bend the by-pass duct and check to see if it will reach from the face of the by-pass template to the side of the humidifier template.  If by-pass duct is not long enough, relocate the template.  If necessary, additional lengths of by-pass ducts are available from your local home center.  Drill (6) 1/8 inch holes as indicated on the templates.  Drill or punch a starter hole and then use a pair of sheet metal snips to cut out the opening.  Remove the templates and tape.

INSTALL HUMIDIFIER

Install (2) 3/4 inch long sheet metal screws halfway in to the two upper most holes that were drilled through the mounting template.  Hang the AUTOFLO model 200P from the two long screws on the top lip.  Install (4) 3/8 inch long  sheet metal screws through the side flange and then tighten all six screws.

INSTALL DUCT ADAPTOR

Mount the duct adaptor to the bypass opening with (2) 3/8 inch long sheet metal screws.  Install the baffle between the duct and the adaptor.  The baffle should be open during the heating and season and closed for cooling season.  Install and tighten the remaining (3) 3/8 inch long screws.

HUMIDIFTAT MOUNTING LOCATION

The humidistat can be mounted on the cold air return duct to sense the cool dry air returning to the furnace.  Mount the humidistat a minimum of 5 feet upstream of the bypass connection to the return air duct.  The humidistat can also be mounted on an interior wall near the furnace thermostat as well.  The electrical connections and basic wiring are the same for duct mounted or wall mounted humidistats.

INSTALL BY-PASS DUCT AND END CAP

Route the flexible by-pass duct from the duct adaptor to the side of the humidifier.  If the provided by-pass duct is not long enough, you can purchase additional by-pass duct at your local home center.  Hard drawn round duct and adjustable fittings can also be used.  Drill two holes through the by-pass duct and duct adaptor and install (2) 3/8 inch long sheet metal screws.  Each of the flanges on both sides of the humidifier have two pre-punched holes.  Use these holes as guides and carefully pierce the by-pass duct from the inside of the humidifier.  Use (2) 3/8 inch long sheet metal screws and attach the end cap to the other end of the humidifier to seal off the unused end.

TYPICAL FIELD CONFIGURATIONS for UP FLOW and HORIZONTAL FLOW FURNACES AND AIR HANDLERS.

Your actual configuration may vary.  Additional by-pass duct may be required, but keep the by-pass duct as short as possible.  The by-pass duct should NEVER be routed across the front of the furnace.  All furnace access doors and openings must remain unobstructed for proper furnace operation and servicing.  Remember to cap off the unused end of the humidifier.

ELECTRICAL CONNECTIONS

The transformer should be wired in parallel with the furnace blower motor line voltage.  This will allow the humidifier to run only when there is a call for fan.  The transformer is designed to be attached to a 4 inch square outlet box.  The electrical box must be mounted and wired in accordance with local building codes and the National Electrical Code.  SHUT OFF THE POWER TO THE FURNACE BEFORE PROCEEDING! NOTE1: Check wiring in furnace for humidifier (HUM) terminals.  If present, check to see if it is 120vac or 24vac.  If it is 120vac, connect on side of the humidistat to one HUM terminal and the other HUM terminal to the motor of the humidifier.  Then make the last connection of the motor to the humidistat.  If you are using the transformer you will need to connect the 24vac common from the transformer to one of the motor wires and then the 24vac hot from the transformer to the humidistat.  Then from the humidistat to the other wire on the motor.  Make sure not to route wires where they can be burned or chaffed.  See example wiring solutions drawing.

OPERATIONAL CHECK

With the humidistat set to its highest setting the motor should start shortly after the furnace blower is activated.  If motor does not start refer to troubleshooting guide in the manual.

CAUTION: Check the transformer, the motor, humidistat, and any other field installed devices, as well as all field wiring. 

A qualified Electrician should be consulted to determine if line voltage is present at the transformer and that 24vac is present at the humidistat and at the motor.

WATER CONNECTION

Water supply for the humidifier must be taken from a nearby water line.  If the humidifier is installed in, above, or adjacent to a decorated living area, an emergency overflow pan is required below the humidifier.   Do not use any line connected to an air conditioning coil.  Lines connected to an a/c coil normally contain refrigerant not water.  Do not use any line serviced by a water softener, make the water connection up stream of a water softener.  A water softener is not a de-mineralizer.  It merely exchanges hard-ions for soft-ions in the water.  These soft-ions or minerals, will build up in the humidifier, causing a need for frequent servicing.  The evaporation of softened water way also produce a white powder which may be carried into the duct work and ultimately in to your home.  You have been supplied with 10 feet of plastic tubing for making the water connection.  If more tubing is needed, longer lengths of 1/4 inch OD plastic or copper tubing is available from your local home center.  Follow the instructions on the saddle for taping valve kit and install the valve.  The valve should be mounted on top or on the side of the water line to prevent the valve from clogging with any sediment from the water line.  Prior to connecting to the float open the valve and flush the water line into a bucket.  This will clear any sediment from the line that may clog or impair the float operation.  Attic installations are not recommended.

FLOAT ADJUSTMENT

Remove the front cover and check the water level.  The float has been set at the factory for normal water pressure conditions.  The float should completely shut off the water flow when the water level is 1-1/4 inches to 1-3/4 inches above the bottom of the pan.  If additional adjustment is needed, adjust the float bulb screw located on top of the float arm above the bulb.  Turn the screw clockwise to lower the water level, turn it counter clockwise to raise the level.  The hex nut may be loosened and the entire float assembly may be moved up or down to adjust the water level.  Adjustment of the crutch screw is not recommended.  You should maintain a water level that is high enough to wet the media wheel as it turns, but not so high that water runs out of the overflow spout.  Refer to the drawing.

DRAIN CONNECTION

We recommend that a drain line be used as an emergency overflow for the model 200P humidifiers.  Use a hose clamp to connect the supplied drain hose to the overflow spout, if available.  The spout is on the right-hand side of the water pan.  Do not use rigid piping because the water pan must be removable for routine cleaning and service.  Keep the hose as short as possible and avoid sharp bends.  The drain line should be routed on a continuous downward slope and into a suitable drain.

SETTING THE HUMIDISTAT

The proper relative humidity for your home depends upon several factors such as outdoor temperature, type and placement of insulation, vapor barriers, quality of windows and doors (including frames and jams), and effectiveness of weather stripping.  With all these variables, it is nearly impossible to recommend a single proper humidity setting.  The best humidistat setting is one that you are comfortable with.

As the outdoor temperature fluctuates, it may be necessary to adjust the humidity level in your home several times during the season.  Refer to the Relative Humidity Chart as a starting point for your proper humidistat setting.  In a tight, well insulated house, the humidistat may be set higher than in a drafty, poorly insulated house.

DO NOT OVER - HUMIDIFY

Cold air cannot hold as much moisture as warm air.  Any cold drafts, or cold-faces such as windows and doors (including frames and jams) may cause water vapor to condense at these points.  Also, if your home is well-insulated and weather-stripped but lacks effective vapor barriers, water way seep through the walls and ceilings.  This moisture may condense either inside or outside the walls or in the attic.  If any of these conditions are observed, the humidity level should be reduced before water damage occurs.  Consider purchasing a model 072000 Smart Humidistat.  The 072000 monitors the outside air temperature and automatically adjusts the RH set point as the outdoor temperature falls below 35 degrees F.

RELATIVE HUMIDITY CHART

Suggested Humidistat Settings

OUTDOOR TEMPERATURE

ADJUST &RH TO

+30o F

40%

+20o F

35%

+10o F

30%

+0o F

25%

-9o F

20%

MAINTENANCE

All power humidifiers require some maintenance to keep them operating at peak performance.  The AUTOFLO model 200P humidifier has been designed to simplify this required maintenance routine.  Proper maintenance of your AUTOFLO humidifier should include the following three procedures:

1.  Annual replacement of the evaporator pad.

2.  An occasional cleaning of the water pan.

3.  An annual cleaning, general inspection, and shut down of the unit.

The evaporative pad should be replaced with catalog # 200EP.  When the pad becomes clogged or brittle it needs to be replaced.  The rate of evaporation depends upon both the surface area of the pad and the ability of the air to pass through the pad.  To remove the pad, turn off power to both the humidifier and the furnace.  Open the service door and lift the rear of the wheel.  Disengage the front of the wheel from the motor and lift the wheel and pad up and out.  To clean the water pan, turn off the water supply valve.  Remove the drain line from the waiter pan.  Locate the two thumb screws which are located on each side of the humidifier.  When you remove these screws the water pan which is full of water will be free to fall downward.  With this in mind, hold the bottom of the pan with one hand and loosen the thumb screws with the other.  Support the water pan in a level position until the water can be dumped into a suitable receptacle.  Remove mineral deposits from the water pan.  A mild detergent or vinegar and water solution is acceptable for cleaning the pan.  When replacing the water pan, the float must be gently lifted into position.  This will prevent damage or bending of the float assembly.  Re-install the two thumb screws to the humidifier, check the float operation and check for leaks.  Annual (spring) shut-down should consist of replacing the evaporator pad, thoroughly cleaning the water pan, and rotating the by-pass baffle to the closed position.  After performing these procedures, leave the water and electrical power off to the humidifier for the summer or cooling season.  To restart the humidifier in the fall, turn on the water supply, power up the humidifier, and rotate the baffle to the open position.  Set your humidistat to the desired setting.




MODEL 200P PARTS LIST



 
PART DESCRIPTION

REPLACEMENT NUMBER
 1. Model 200P Humidifier
 
 2. Small parts bag containing:
     a. Two #8 x 3/4 in. sheet metal screws
     b. Seventeen #8 x 3/8 in. sheet metal screws
     c. Strain Relief
     d. Two wire nuts
 
 3.  24vac transformer
 
 4.  End Cap
 
 5.  Baffle
 
 6.  Duct adaptor
 
 7.  1/4 inch plastic tubing
 
 8.  Saddle taping valve kit
 
 9.  Mounting template (not shown)  
 10.  By-pass adaptor template (not shown)

 11. Autoflo 24vac humidistat
 
 12. Drain tubing
 

ADDITIONAL RECOMMENDED PARTS




 
PART DESCRIPTION

REPLACEMENT NUMBER
 1.  Current sensing relay
 
 2.  Small hose clamp for drain tubing
 
 3.  Electrical wire and enclosures for
      both line voltage and 24vac
      connections
 
















=
 Owner's Manual
Mounting Template
   
 
     
       
       